Product type designation |
OSM ITP62-LD |
Product description |
|
|
SIMATIC NET, OSM ITP62-LD OPTICAL SWITCH MODULE W. 2 FOC PORTS 100 MBIT/S LONG DISTANCE (FOC UP TO 26 KM),6 ITP PORTS 10/100 MBIT/S AND 8 DIGITAL INPUTS; REDUNDANT 24V DC SUPPLY, SIGNAL CONTACT, INTEGRATED REDUNDANCY MANAGER WITH NETWORK MANAGEMENT AMBIENT TEMPERATURE MAX. +55 DEGR. C. |
Transmission rate |
Transfer rate |
10 Mbit/s, 100 Mbit/s |
Interfaces |
Number of electrical/optical connections |
|
● for network components or terminal equipment / maximum |
8 |
Number of electrical connections |
|
● for network components or terminal equipment |
6 |
● for signaling contact |
1 |
● for power supply |
1 |
● for redundant voltage supply |
1 |
Design of the electrical connection |
|
● for network components or terminal equipment |
9-pin Sub-D socket (10/100 Mbit/s) |
● for signaling contact |
On 6-pole terminal block |
● for power supply |
6-pole plug-in terminal block |
Number of optical interfaces |
|
● for fiber optic cable / at 100 Mbit/s |
2 |
Design of the optical interface |
|
● for fiber optic cable / at 100 Mbit/s |
BFOC port (singlemode up to 26 km) |
Signal-Inputs/outputs |
Operating voltage / of the signaling contacts |
|
● for DC / Rated value |
24 V |
Operating current / of the signaling contacts |
|
● for DC / maximum |
0.1 A |
Number of digital inputs |
8 |
Number of electrical connections / for digital input signals |
2 |
Design of the electrical connection / for digital input signals |
4-pole plug-in terminal block |
Signal voltage |
|
● for signal <0> / for DC |
-30 ... +3 V |
— Rated value |
24 V |
● for signal <1> / for DC |
13 ... 30 V |
— Rated value |
24 V |
Input current / at digital input |
|
● with signal <0> / maximum |
0.008 mA |
● for signal <1> |
0.008 A |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage |
DC |
Supply voltage |
|
● external |
24 V |
● external |
18 ... 32 V |
Product component / fusing at power supply input |
Yes |
Fuse protection type / at input for supply voltage |
T 1,6 A / 250 V |
Consumed current / maximum |
1 A |
Active power loss |
|
● for DC / at 24 V |
20 W |
Permitted ambient conditions |
Ambient temperature |
|
● during operation |
0 ... 60 °C |
● during storage |
-20 ... +80 °C |
● during transport |
-20 ... +80 °C |
Relative humidity |
|
● at 25 °C / without condensation / during operation / maximum |
95 % |
Protection class IP |
IP20 |
Design, dimensions and weight |
Width |
217 mm |
Height |
161 mm |
Depth |
69 mm |
Net weight |
1.4 kg |
Mounting type |
|
● 35 mm DIN rail mounting |
Yes |
● wall mounting |
Yes |
● S7-300 rail mounting |
No |
● S7-1500 rail mounting |
No |
● fixed-mounted |
Yes |
Product properties, functions, components / general |
Cascading in the case of a redundant ring / at reconfiguration time of <~0.3~s |
50 |
Cascading in cases of star topology |
Any (depending only on signal propagation time) |
Product functions / management, configuration |
Product function |
|
● CLI |
Yes |
● web-based management |
Yes |
● MIB support |
Yes |
● TRAPs via email |
Yes |
● RMON |
Yes |
● Port mirroring |
Yes |
● multiport mirroring |
No |
● switch-managed |
Yes |
Protocol / is supported |
|
● Telnet |
Yes |
● HTTP |
Yes |
● TFTP |
Yes |
● FTP |
Yes |
● BOOTP |
Yes |
Protocol / is supported |
|
● SNMP v1 |
Yes |
Product functions / Diagnosis |
Product function |
|
● Statistics Packet Size |
Yes |
● Statistics packet type |
Yes |
● Error statistics |
Yes |
Product functions / DHCP |
Product function |
|
● DHCP client |
Yes |
Product functions / Redundancy |
Product function |
|
● Ring redundancy |
Yes |
● High Speed Redundancy Protocol (HRP) |
Yes |
● high speed redundancy protocol (HRP) with redundancy manager |
Yes |
● high speed redundancy protocol (HRP) with standby redundancy |
Yes |
● media redundancy protocol (MRP) with redundancy manager |
Yes |
Product functions / Time |
Product function |
|
● SICLOCK support |
Yes |
Standards, specifications, approvals |
Standard |
|
● for FM |
FM3611: Class 1, Divison 2, Group A, B, C, D / T.. A, CL.1, Zone 2, GP. IIC, T4 |
● for safety / from CSA and UL |
UL 60950-1, CSA C22.2 No. 60950-1 |
● for emitted interference |
EN 61000-6-4 |
● for interference immunity |
EN 61000-6-2 |
Certificate of suitability |
|
● CE marking |
Yes |
● C-Tick |
Yes |
● KC approval |
No |
Marine classification association |
|
● American Bureau of Shipping Europe Ltd. (ABS) |
Yes |
● Bureau Veritas (BV) |
Yes |
● Det Norske Veritas (DNV) |
Yes |
● Germanische Lloyd (GL) |
Yes |
● Lloyds Register of Shipping (LRS) |
Yes |
● Nippon Kaiji Kyokai (NK) |
Yes |
● Polski Rejestr Statkow (PRS) |
Yes |
Further Information / Internet Links |
Internet-Link |
|
● to website: Selector SIMATIC NET SELECTION TOOL |
http://www.siemens.com/snst |
● to website: Industrial communication |
http://www.siemens.com/simatic-net |
● to website: Information and Download Center |
http://www.siemens.com/automation/net/catalog |
● to website: Image database |
http://automation.siemens.com/bilddb |
● to website: CAx Download Manager |
http://www.siemens.com/cax |
● to website: Industry Online Support |
http://support.automation.siemens.com |
Security information |
Security information |
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit http://www.siemens.com/industrialsecurity. To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com. (V3.4) |
last modified: |
04.11.2014 |
Date 06.11.2014 |
Changes preserved © Copyright Siemens AG 2014 |